RITTAL Enclosure Cooling Unit Error Code Table

In order to help you fix the troubleshooting of RITTAL cooling units with Comfort Controller. A more detailed explanation of the system messages are shown on the display screen via the displays from A1 to A20 as the table below:

RITTAL Enclosure Cooling Unit Error Code Table

In order to help you fix the troubleshooting of RITTAL cooling units with Comfort Controller. A more detailed explanation of the system messages are shown on the display screen via the displays from A1 to A20 as the table below: 

RITTAL COMFORT CONTROLLER TROUBLESHOOTING 
Display Screen System Message Possible Cause Measures to Rectify the Fault
A01 Enclosure door open

a) Door open

b) Door limit switch incorrectly positioned

a) Close door

b) Position door limit switch correctly, check connection if necessary

A02 Internal temperature
of enclosure too high
a) Cooling capacity inadequate/unit undersized. b) Error as a consequence of messages A03 to A17. a) Check cooling capacity
b) Checking from A03 to A17.
A03 Filter monitoring  Filter mat soiled Clean or replace, reset the comfort controller
A04 Ambient temperature
too high/too low
Ambient temperature outside of admissible operating range (+10°C to +60°C) Raise or lower the ambient temperature (e.g. heat or ventilate the room)
A05  Icing hazard a) Operational display in case of icing hazard. 
b) Evaporator coil fan may be mechanically blocked, defective, or cold air outlet obstructed. 

a) Set the enclosure interior temperature to a higher value.

b) Check the evaporator fan, release or exchange if necessary.

A06 PSA H pressure-operated
switch
a) Ambient temperature too high
b) Condenser soiled
c) Filter mat soiled
d) Condenser fan defective
e) E-valve defective
f) PSA H  pressure-operated switch defective

a) Lower the ambient temperature; reset the Comfort controller

b) Clean the condenser; reset the Comfort controller

c) Clean or replace; reset the Comfort controller

d) Replace; reset the Comfort controller

e) Have the sensor repaired by a refrigeration engineer; reset the Comfort controller

f) Have the switch replaced by a refrigeration engineer; reset the Comfort controller

A07 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. Have the sensor repaired by a refrigeration engineer; reset the Comfort controller
A08 Condensate warning a) Condensate discharge kinked or blockedb) Only in units with optional condensate evaporation

a) Check condensate discharge; repair any kinks or blockages in the hose as necessary

b) Check the evaporation unit, exchange if necessary

A09 Condenser fan  Blocked or defective Clear the blockage; replace if necessary
A10 Evaporator fan Blocked or defective Clear the blockage; replace if necessary
A11
Compressor

a) Compressor overloaded
(internal winding protection)

b) Defective (check by measuring the winding resistance)

a) No action required; unit switches back on automatically.

b) Exchange by refrigeration engineer

A12 Condenser temperature
sensor
Open or short-circuit Replace
A13 Ambient temperature
sensor
Open or short-circuit Replace
A14 Icing temperature sensor Open or short-circuit Replace
A15 Condensate warning
temperature sensor
Open or short-circuit Replace
A16 Internal temperature sensor Open or short-circuit Replace
A17 Phase monitoring For three-phase devices only:
Incorrect rotary field/phase absent
Exchange two phases
A18 EPROM error New board obstructed Software update needed (only following board installation with more recent software): Enter the programming level with Code 22; press button 1 and confirm with “Set” until “Acc” appears. Next, disconnect the unit from the mains and reconnect.
A19 LAN/Master-slave Master and slave not connected Check setting and/or cable
A20 Voltage drop Error display not shown Event is stored in the log file
EO Display message a) Connection problem between the display and the controller board         b) Cable defective; connection loose

a) Reset: Switch power supply off, then switch on again after approx. 2 sec.

b) Exchange the boards

OL Overload Ambient parameters or heat loss outside of the applicable limits
LH Low heat Minimal heat loss inside the enclosure
rSt Reset Manual device reset required, see “6.2.9 Resetting the Comfort controller”, page 32.